14.0 kW Cooling
16.0 kW Heating
Power Inverter | ZM Series
Specifications
Ceiling-Concealed (PEAD-ZM Series) | ||||
Indoor Unit | PEAD-M140JAA(D) | |||
Outdoor Unit
Refrigerant |
PUZ-ZM 140YKA | |||
R32 | ||||
Power Supply | V:230V, Single-phase, 50Hz Y:400V, Three-phase, 50Hz | |||
Capacity | (kW) | 6.2-14.0-15.3 | ||
[Min-Rated-Max] | ||||
Total Input [Rated] | (kW) | 4.37 | ||
AEER/EER | 3.09 / 3.20 | |||
Cooling | AEER [Part-load %] *1 | 4.09 | ||
7.40 | ||||
Running Current [Rated] | A | |||
Sound In (Lo-Mid-Hi)
Pressure |
dB(A) |
40-44-49 | ||
Level Out (PWL) | 50 (70) | |||
Air Volume (In) Lo-Mid-Hi | L/S | 533-650-767 | ||
Capacity |
(kW) |
5.7-16.0-18.0 |
||
[Min-Rated-Max] | ||||
Total Input [Rated] | (kW) | 4.18 | ||
Heating |
ACOP/COP
Running Current [Rated] (mm) |
3.69 / 3.82 | ||
7.10 | ||||
Sound In (Lo-Mid-Hi) | dB(A) | 40-44-49 | ||
Level Out (PWL)
Air Volume (In) Lo-Mid-Hi |
dB(A) | 52 (71) | ||
533-650-767 | ||||
Max. Running Current | A | 14.10 | ||
Indoor Unit |
Input [Rated] | kW | (0.39) / 0.37 | |
Dimensions [HxWxD] | mm | 250 x 1600 x 732 | ||
Weight | kg | 44 | ||
Static Pressure | Pa | 35 / 50 / 70 / 100 / 125 | ||
Outdoor Unit |
Dimensions [HxWxD] | mm | 1338 x 1050 x 330 (+40) | |
Weight | kg | 112 | ||
Breaker Size | A | 16 | ||
Ext. Piping | Diameter [Gas/Liquid] | mm | 15.88 / 9.52 | |
Max. Length/Height | m | 75 / 30 | ||
Guaranteed Cooling *2 | °C | -5(-15) ~ 52 | ||
Operating Range
[Outdoor] Supply Air Duct |
Heating | °C | -20 ~ 21 | |
mm | 1560 x 178 | |||
Precharge Refrigerant | kg | 4 (30m) | ||
Additional Refrigerant |
per M(g) |
40 |