MITSUBISHI ELECTRIC PEAMS100GAAVKIT 10.0kW Ducted Air Conditioner System 1 Phase

Mitsubishi Electric Ducted System

10.0kW Cooling – 11.2kW Heating Capacity. PEAMS100GAAVKIT . Indoor PEA-M100GAA.TH – Outdoor PUZ-M100VKA-A.TH Single Phase / PAR-40MAA Controller

Single Fan Outdoor Unit.

Single Fan Outdoor | New Model M Series

Specifications

Ceiling-Concealed (PEA-M/ZM Series)
Indoor Unit PEA-M100GAA
Outdoor Unit

 

 

Refrigerant

PUZ-M 100VKA
R32
 

 

 

Power Supply

Source Outdoor power supply
 

 

Outdoor

V: 230V,

 

Single-phase, 50Hz

Indoor
 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

Heating

Capacity

 

[Min-Rated-Max]

(kW) 4.0-10.0-10.6
Total Input [Rated] (kW) 3.08
AEER/EER 3.24 / 3.12
AEER [Part-load %] *1 4.40
 

 

Running Current [Rated]

 

 

A

 

 

14.5

Sound In (Lo-Mid-Hi)  

 

dB(A)

33-38-42
Pressure

 

Level

Out (PWL) 52 (71)
Air Volume (In) Lo-Mid-Hi L/S 567 – 700
Capacity

 

[Min-Rated-Max]

(kW) 2.8-12.5-12.5
Total Input [Rated] (kW) 3.36
ACOP/COP *3 3.72 / 3.58
Running Current [Rated] (mm) 15.8
Sound Pressure In (Lo-Mid-Hi) dB(A) 39 – 42
Level Out (PWL) dB(A) 54 (72)
Air Volume (In) Lo-Mid-Hi 567 – 700
Max. Running Current A 23.28
Input [Rated] kW 0.21 / 0.21
Indoor Unit Dimensions [HxWxD] mm 400 × 1400 × 634
Weight kg 63
Static Pressure Pa 50 / 100 / 150
 

 

Outdoor Unit

Dimensions [HxWxD] mm 981 x 1050 x

 

330 (+40)

Weight kg 76
Breaker Size A 32
Ext. Piping Diameter [Gas/Liquid] mm 15.88 / 9.52
Max. Length/Height m 55 / 30
Guaranteed Operating Range [Outdoor] Cooling *2 °C -5 (-15) ~ 46
Heating °C -15 ~ 21
Supply Air Duct mm 921 x 250
Return Air Duct mm 1102 x 330
Precharge Refrigerant kg 3.1 (30m)
Additional Refrigerant Per M (g) 200