Overview

MITSUBISHI ELECTRIC PEAD-M100JAADR1.TH / PUZ-ZM100VKA-A.TH 10kW Ducted Air Conditioner System 1 Phase

PEAD-M100JAADR1.TH : Indoor – Ducted with Drain Pump
PUZ-ZM100VHA-AR1 : R32 Power Inverter Outdoor – Single Phase
PAR-40MAA : Wired Control with Back Light

10.0 kW Cooling
11.2 kW Heating

Power Inverter | ZM Series

Specifications

Ceiling-Concealed (PEAD-ZM Series)
Indoor Unit PEAD-M100JAA(D)
Outdoor Unit

 

 

Refrigerant

PUZ-ZM 100VKA
R32
Power Supply V:230V, Single-phase, 50Hz Y:400V, Three-phase, 50Hz
Capacity (kW) 4.9-10.0-11.4
[Min-Rated-Max]
Total Input [Rated] (kW) 2.67
AEER/EER 3.60 / 3.74
Cooling AEER [Part-load %] *1
12.20
Running Current [Rated] A
Sound       In (Lo-Mid-Hi)

 

Pressure

 

 

dB(A)

33-38-42
Level         Out (PWL) 49 (69)
Air Volume (In) Lo-Mid-Hi L/S 400-483-567
Capacity  

 

(kW)

 

 

4.5-11.2-14.0

[Min-Rated-Max]
Total Input [Rated] (kW) 2.80
 

 

Heating

ACOP/COP

 

Running Current [Rated] (mm)

3.86 / 4.00
12.70
Sound       In (Lo-Mid-Hi) dB(A) 33-38-42
Level         Out (PWL)

 

Air Volume (In) Lo-Mid-Hi

dB(A) 51 (69)
400-483-567
Max. Running Current A 29.18
 

 

 

Indoor Unit

Input [Rated] kW (0.25) / 0.23
Dimensions [HxWxD] mm 250 x 1400 x 732
Weight kg 39
Static Pressure Pa 35 / 50 / 70 / 100 / 125
 

 

Outdoor Unit

Dimensions [HxWxD] mm 1338 x 1050 x 330 (+40)
Weight kg 111
Breaker Size A 32
Ext. Piping Diameter [Gas/Liquid] mm 15.88 / 9.52
Max. Length/Height m 75 / 30
Guaranteed               Cooling *2 °C -5(-15) ~ 52
Operating Range

 

[Outdoor]

Supply Air Duct

Heating °C -20 ~ 21
mm 1360 x 178
Precharge Refrigerant kg 4 (30m)
 

 

Additional Refrigerant

per M(g)  

 

40