Daikin
DAIKIN FCA50CA-VC2V 5kW Premium Reverse Cycle Cassette System - 1 Phase
Overview
DAIKIN FCA50CA-VC2V 5kW Premium Reverse Cycle Cassette System
The DAIKIN FCA50CA-VC2V 5kW Premium Inverter Reverse Cycle Cassette System offers exceptional climate control with a sleek and discreet design. With 5.0kW cooling and 6.0kW heating capacities, this single-phase system is perfect for maintaining year-round comfort in various spaces. Equipped with a durable fascia and a user-friendly controller, it integrates seamlessly into any environment. Ideal for Australian homes and businesses, this system ensures reliable performance with minimal visual impact.
Indoor: FCA50CAVMA
Outdoor: RZAV50C2V1
Fascia: BYCQ125EAF
Controller: BRC1E63
Specifications
Indoor Unit | FCA50CAVMA | |||||||
Outdoor Unit | RZAV50C2V1 | |||||||
Power Supply | ø / V / Hz | 1 Phase, 240V, 50 Hz | ||||||
Cooling Capacity | Rated (Min – Max) | kW | 5.0 (1.4 – 6.0) | |||||
Heating Capacity | Rated (Min – Max) | kW | 6.0 (1.4 – 7.1) | |||||
Power Consumption | Cooling | kW | 1.11 | |||||
Heating | kW | 1.27 | ||||||
Enery Efficiency | EER | kW | 4.51 | |||||
COP | kW | 4.73 | ||||||
Indoor Unit | Colour | Unit | – | |||||
Decoration Panel | Fresh White | |||||||
Airflow Rate (H / HM / M / ML / L) | L/s | 383 / 350 / 308 / 267 / 225 | ||||||
m³/min | 23.0 / 21.0 / 18.5 / 16.0 / 13.5 | |||||||
Sound Level (H/M/L) | dB(A) | 37.0 / 36.0 / 34.0 / 31.0 / 27.5 | ||||||
Dimensions (HxWxD) | Unit | mm | 256 x 840 x 840 | |||||
Decoration Panel | mm | 50 x 950 x 950 | ||||||
Machine Weight | Unit | kg | 22 | |||||
Decoration Panel | kg | 5.5 | ||||||
Certified Operation Range | Cooling | °CWB | 14 to 25 | |||||
Heating | °CDB | 15 to 27 | ||||||
Outdoor Unit | Colour | Ivory white | ||||||
Compresser | Type | Hermetically sealed swing type | ||||||
Motor output | kW | 1.3 | ||||||
Refrigerant Charge (R410a) | kg | 1.35 (charged for 30m) | ||||||
Sound Level | Cooling / Heating | dB(A) | 48 / 51 | |||||
Night quiet mode | dB(A) | 44 | ||||||
Sound Power Level (H/L) | dB(A) | 68 | ||||||
Dimensions (HxWxD) | mm | 595 x 845 x 300 | ||||||
Machine Weight | kg | 45 | ||||||
Certified Operation range | Cooling | °CDB | -5 to 50 | |||||
Heating | °CWB | -15 to 15.5 | ||||||
Piping Connections | Liquid (Flare) | mm | ø6.4 | |||||
Gas (Flare) | mm | ø12.7 | ||||||
Drain | Indoor Unit | mm | I.D. ø25 x O.D ø32 | |||||
Outdoor Unit | mm | ø26.0 (Hole) | ||||||
Refrigerant | R32 | |||||||
Max, interunit piping length | m | 50 (Equivalent length 70) | ||||||
Max. Installation level difference | m | 30 | ||||||
Heat insulation | Both liquid and gas piping |